RCI Mobile Purification Equipment

Using a combination of RCI’s purifiers, coalescers, and filters can deliver polished fuel that’s 99.99% free of water and particulates. From here, polished fuel can be conditioned by infusion of additives to accommodate operational parameters. Additives, such as antimicrobials, stabilizers, lubricants, and other add-ons to improve fuel C-TANE rating, can be introduced safely.

 

PFPU-8

There are no translations available.

pffu-8

The PFPU-8 is an 8 gpm portable contaminant removal system for use in both above- and below-ground fuel storage tanks. It is designed specifically to remove water and other heavy contaminants common to stored diesel fuel and will fit through doorways and up stairways. It can be used in almost any location, from rooftop to shipboard. This unit requires 12/24 VDC power.

The PFPU-8 is factory preassembled and consists of an RCI FP 800 fuel purifier, a self-priming pump, a UL-approved motor, a panel with drip tray, and suction and return hoses. It utilizes RCI’s patented fuel purification technology and is used as primary fuel purification, with the ability to remove up to 99.8% of free water and up to 95% of other heavy contaminants, down to approximately 10 microns.

SPECIFICATIONS:

Flow Rate: 8 gpm

RCI Purifier: FP 800

Water Removal: up to 99.8% of free water

Particulate Removal: up to 95% of heavy contaminants

Dimensions: 20" H x 19" W x 15" D

Drain Port:1/2"

Motor Max Pump Pressure: 78 psi

Motor Horse Power: 1/5

Suction Hose: 3/4" x 10' detachable suction hose

Manual Shut-Off Nozzle: 3/4"

Power Requirements: 12 VDC

Power Cord: 15'

Weight: 45 lbs.

PFPU-25

There are no translations available.

pfpu-20

The PFPU-25 is a 25 gpm portable contaminant removal system for use in both above- and below-ground fuel storage tanks. It is designed specifically to remove water and other heavy contaminants common to stored diesel fuel and will fit through doorways and up stairways. It can be used in almost any location, from rooftop to shipboard.

The PFPU-25 is factory preassembled and consists of an RCI FP 1000 fuel purifier, a self-priming pump, a UL-approved motor, a portable hand cart, and suction and return hoses. It utilizes RCI’s patented fuel purification technology and is used as primary fuel purification, with the ability to remove up to 99.8% of free water and up to 95% of other heavy contaminants, down to approximately 10 microns.

For advanced filtration, we offer the following options: bag filter for sludge removal, high-efficiency fuel filter, three-phase fuel coalescer with a 99.5% single-pass water removal efficiency, and power upgrades.

SPECIFICATIONS:

Flow Rate: 25 gpm

RCI Purifier: FP 1000

Water Removal: up to 99.8% of free water

Particulate Removal: up to 95% of heavy contaminants

Dimensions: 50" H x 22" W x 31" D

Drain Port: 1/2"

Motor Max Pump Pressure: 78 psi

Motor Horse Power: 1/3 hp

Suction Hose: 3/4" x 20' detachable suction hose

Manual Shut-Off Nozzle: 3/4"

Power Requirements: 12/24 VDC, 50 or 60 Hz, single-phase

Power Cord: 25 foot

Weight: 170 lbs.

Options: Bag filter for sludge removal, high-efficiency fuel filter, three-phase fuel coalescer, and power upgrades

PFPU-20

There are no translations available.

pfpu-20

The PFPU-20 is a 20 gpm portable contaminant removal system for use in both above- and below-ground fuel storage tanks. It is designed specifically to remove water and other heavy contaminants common to stored diesel fuel and will fit through doorways and up stairways. It can be used in almost any location, from rooftop to shipboard.

The PFPU-20 is factory preassembled and consists of an RCI FP 1000 fuel purifier, a self-priming pump, a UL-approved motor, a portable hand cart, and suction and return hoses. It utilizes RCI’s patented fuel purification technology and is used as primary fuel purification, with the ability to remove up to 99.8% of free water and up to 95% of other heavy contaminants, down to approximately 10 microns.

For advanced filtration, we offer the following options: bag filter for sludge removal, high-efficiency fuel filter, three-phase fuel coalescer with a 99.5% single-pass water removal efficiency, and power upgrades.

SPECIFICATIONS:

Flow Rate: 20 gpm

RCI Purifier: FP 1000

Water Removal: up to 99.8% of free water

Particulate Removal: up to 95% of heavy contaminants

Dimensions: 50" H x 22" W x 31" D

Drain Port: 1/2"

Motor Max Pump Pressure: 78 psi

Motor Horse Power: 1/3 hp

Suction Hose: 3/4" x 20' detachable suction hose

Manual Shut-Off Nozzle: 3/4"

Power Requirements: 115/230 VAC, 60 Hz, single-phase

Power Cord: 25 foot

Weight: 200 lbs.

Options: Bag filter for sludge removal, high-efficiency fuel filter, three-phase fuel coalescer, and power upgrades

PFPU-50

There are no translations available.

pfpu-50

The PFPU-50 is a high-volume 50 gpm portable contaminant removal system for use in both above- and below-ground fuel storage tanks. It is designed specifically to remove water and other heavy contaminants common to stored diesel fuel and will fit through doorways and up stairways. It can be used in almost any location, from rooftop to shipboard.

The PFPU-50 is factory preassembled and consists of an RCI FP 1500 fuel purifier, a self-priming pump, a UL-approved motor, a portable hand cart, and suction and return hoses. It utilizes RCI’s patented fuel purification technology and is used as primary fuel purification, with the ability to remove up to 99.8% of free water and up to 95% of other heavy contaminants, down to approximately 10 microns.

For advanced filtration, we offer the following options: bag filter for sludge removal, high-efficiency fuel filter, three-phase fuel coalescer with a 99.5% single-pass water removal efficiency, and power upgrades.

SPECIFICATIONS:

Flow Rate: 50 gpm

RCI Purifier: FP 1500

Water Removal: up to 99.8% of free water

Particulate Removal: up to 95% of heavy contaminants

Dimensions: 50" H x 25" W x 31" D

Drain Port: 1/2"

Motor Max Pump Pressure: 78 psi

Motor Horse Power: 1/5 hp

Suction Hose: 3/4" x 20' detachable suction hose, explosion proof

Manual Shut-Off Nozzle: 1-1/2"

Power Requirements: 115/230 VAC, 50 or 60 Hz, single-phase

Power Cord: 25 foot

Weight: 305 lbs.

Options: Bag filter for sludge removal, high-efficiency fuel filter, three-phase fuel coalescer, and power upgrades